CP110-GM

CP110-GM

PUMP CONTROLLING DEVICE

cp110-gm
      • kuyu
      • terfi
      • surucu
      • verimlilik
      • oransal
      • TECHNICAL SPECIFICATIONS

        The Specifications of the PLC Controller:• 9 channel 24VDC PNP/NPN input
        • 6 channel 230VAC 5A relay output
        • 1 channel 0-10VDC/0-20mADC optional analog input (12-bit resolution)
        • 1 channel 0-20mADC analog output (14-bit resolution)
        • Can be expanded by maximum 16 expansion units due to the modular structure
        • Communication over the network via a 100MBit ethernet port
        • MODBUS TCP support
        • RS232 ve RS485 communication ports
        • MODBUS RTU support
        • Decimal operation support
        • 12ns processing speed
        • RTC (Real Time Clock)
        • Supplied by 24VDC
        • Power Consumption < 3W
        • Working temperature between 0°C and +50°C
        • Can be programmed with Ladder Logic Diagram Editor
        Power Supply:• 2.5A, 60W SMPS
        • 24VDC Output, 100-240VAC or 90 350VDC Input
        • Efficiency %88
        • Over power protection, over voltage protection
        • Working temperature between -25°C and +60°C
        Uninterruptible Power Supply:• DC UPS
        • Input 22.5V-28V, Output 24V
        • Output current 30A
        • At least 7 Ah 12V dry accumulator
        • Working temperature is between -40°C and +70°C
        GSM Communication:• 3G Industrial Router
        • Communication speed; 3G 14.4Mbps, 2G 236.8 Kbps
        • IEEE 802.11b/g/n, can be used as Wifi access point or station
        • 2 Ethernet ports
        • Routing, network protocols, firewall, DHCP, QoS, network backup, load balancing, DDOS prevention,
        port scanning prevention, WPA-2Ent Wifi
        encryption, mobile quota control, web filters, access control, VPN, APN
        • RutOS: Linux-based operating system
        • 1 digital input, 1 digital output
        • Operates with 9-30VDC
        • Power consumption < 5W
        • Working temperature is between -40°C and +75°C
        Energy Analyzer:• The measured parameters are: 3xV, 3xI, Frequency, W, Var, VA, kWh, kVarh, Min, Max, Demand, Cos φ
        • RS485 Modbus RTU Communication
        • LCD Screen
        • Sensitivity %0.5
        • Power Consumption < 4W
        • Working temperature is between -10°C and +55°C
        Analog Expansion Module:• 4 Channel 0-10VDC, 0-20mA, 4-20mA analog input
        • 2 Channel 0-10VDC, 0-20mA, 4-20mA analog output
        • The channels can be used as different input/output
        types independent of one another
        • Inputs and outputs are isolated by galvanization
        • 14-bit resolution
        Malfunction Indicators and Buttons:• 2 LEDs for malfunction indicator and run indicator
        • 3-step button (Koru1000 SCADA, Service/Stop mode, manual start mode)
        Panel Specifications and Dimensions:• PVC 40x60x22 cm
        Panel Weight:• 10,25 Kg


      • ABILITIES

        Where can I use this product?• Drinking water applications
        • Agricultural irrigation applications
        • Management of process water
        In what kind of stations, I can use this product?• Well Pump Control
        • Lift Pump Control
        Automatic Operating Scenarios• Can work automatically depending on the linked water reservoir (Koru1000 Link)
        • Can work as booster pump (hydrophore mode)
        • Can work according to a time table
        Sensor supportUp to 4 analog sensors can be connected:
        • Flowmeter
        • Input pressure, output pressure, line pressure
        • Ground water level, reservoir level sensors
        • Remaining chlorine
        • Turbidity
        What happens when the communication is interrupted?Works automatically according to the determined time periods
        Hardware upgradeable?Yes
        7/24 system support?Yes
        Driver (frequency convertor) supportYes(Adaptive PID can be performed with respect to pressure, flow, ground water level or power.)
        Proportional actuator valve controlYes (1)
        Hardware upgradeable?Yes
        7/24 sistem desteğiYes
        Software supportIntegration to the Koru1000 water management system over Koru1000 cloud.
        External SCADA supportIntegration to all SCADA systems that supports Modbus TCP



        Copyright@2018, ENVEST. | All Rights Reserved.